Power Batteries, AGM and GEL VRLA Batteries for mobility, golf, scooters, wheelchair, golf trolleys, emergency lighting, lifts, marine, security alarms and RVs, recreational vehicles. UPS, Broadband and boats.

the CV SERIES

INTRODUCTION

The VRLA, 20 year class battery of choice for High Critical Telecom, Standby, Renewable Energy and Switchgear Tripping Applications. Supplied as Modular Stackable Steel Modules with all Connectors. Available in 27 x 2V types at ratings from 210 to 5040AH. AGM and GEL Version and Extended Warranty options are available.

APPLICATIONS

  • Telecom, wired and wireless.
  • UPS.
  • Switchgear.
  • Renewable Energy.
  • Emergency Lighting.
cv

FEATURES
Design Life - 20 years in float service at 77° F (25° C)
Patented catalyst in each cell - Improves life by lowering float current, reducing grid corrosion and reducing water loss. It°s effects are even more apparent in higher temperatures.
Separators - Micro porous glass mat, H&V is standard.
Plate protection - Plate growth without damage is allowed by a collapsible bridge installed in the bottom of the container.
Electrolyte - Sulphuric acid solution, 1.300 s.g, when fully charged.
Float Voltage - 2.25 volts per cell at 77° F (25° C).
Self-discharge rate - 2% per month at 77° F (25° C).
Intercell connectors - Plated copper BUSBARS.
Internal air passages - Aid heat dissipation, and ensure consistent cell temperatures.
Cell fronts - Protected with a transparent, FR plastic cover.
Modules - Stackable to 8 high while certified to UBC seismic zone 4, Welded steel construction, Internal air passages aid heat dissipation, ensure consistent cell temperatures, Coated with an acid resistant powdered epoxy.

SPECIFICATIONS
Design Life - 20 years in float service at 77° F (25° C).
Cell Type - VRLA, with AGM method of electrolyte immobilisation.
Grids - Positive – proprietary, lead calcium Negative - lead calcium.
Container and cover - impact resistant polypropylene with FR to UL 94 V0 optional.
Post Seals - 2 part epoxy, 2 stage application
Jar to cover seal - heat bonding method (Hardigg Machine).
Leak test method - 100% of cells, with pressurised hydrogen
Safety Valve - opens at 2.5 psi, closes at 2 psi, with flame arrestor in each valve. The Bunsen design is used.

Download Power CV Series Data Brochure

Back to Summary Page

©2008 Power Batteries Ltd        Telephone: +44 (0)1794 835900       Email: sales@powbat.co.uk
Privacy Policy & Disclaimer

[Home] [Battery Types] [Frequent Questions] [Contact Us] [News] [Technical Data] [Terms & Conditions] [On Line Shop] [Privacy Policy] [Battery Types] [Power Batteries High Rate Series] [Power Batteries Premium High Rate Series] [Power Batteries Telecom Series] [Power Batteries Broadband Series] [Power PM Series] [Power Mobility Series] [Power Solar Series] [Power Marine Series] [Power PRC Series] [Power Batteries CV Series] [Power Accessories]